TY - JOUR T1 - Sizing and Cost Assessment of Solar PV System for Energy Supply in the Telecommunication Industry in Nigeria AU - Eng, M. AU - Akinpelu, Emmanuel O. JO - Journal of Engineering and Applied Sciences VL - 6 IS - 2 SP - 130 EP - 134 PY - 2011 DA - 2001/08/19 SN - 1816-949x DO - jeasci.2011.130.134 UR - https://makhillpublications.co/view-article.php?doi=jeasci.2011.130.134 KW - sensitivity analysis KW -generator KW -life cycle cost KW -grid utility KW -diesel KW -Base transceiver station AB - Electrical power from the grid is unreliable in Nigeria. This has forced mobile telecommunication operators to depend mainly on diesel generators. In this research, solar PV system is considered as an alternative power supply option. The PV system to power a Base Transceiver Station (BTS) was sized then Life Cycle Cost (LCC) method of economic assessment was used to compare the cost with the costs of diesel generator and grid utility over the life cycle period of the PV system which is 30 years. The LCC of PV system is $0.84/kWh that of diesel generator, $1.8/kWh and grid utility, $0.063/kWh. Sensitivity, analysis was carried out using variations in module costs, diesel fuel escalation and grid utility escalation. The results suggest that the PV system is cheaper than the diesel generator and could be the best option out of the three in the future. ER -