files/journal/2022-09-02_12-54-44-000000_354.png

Journal of Engineering and Applied Sciences

ISSN: Online 1818-7803
ISSN: Print 1816-949x
110
Views
0
Downloads

Voltage Dips Reduction in the Nigeria 330 kV Transmission Grid

O.S. Onohaebi and S.O. Igbinovia
Page: 496-503 | Received 21 Sep 2022, Published online: 21 Sep 2022

Full Text Reference XML File PDF File

Abstract

This study carried out an in-depth study and analysis of voltage dips associated with Nigerian 330 kV transmission network. The research methodology involved the power flow analysis of the network and subjecting it to contingency analysis and simulation using Newton-Raphson method in Power World Simulator (PWS) environment. The study revealed that the existing network have voltages as low as 217 kV at some buses. The proposed modifications to the 330 kV transmission network which incorporated some additional lines to form more loops and minimal compensation, meet the acceptable voltage limits of ±5%, have positive impact on voltage dips and enhance reliability and security of the transmission grid.


How to cite this article:

O.S. Onohaebi and S.O. Igbinovia . Voltage Dips Reduction in the Nigeria 330 kV Transmission Grid.
DOI: https://doi.org/10.36478/jeasci.2008.496.503
URL: https://www.makhillpublications.co/view-article/1816-949x/jeasci.2008.496.503